More info
Full Description
Scope
This project will provide a revision of the current C37.20.1 Standard. The current revision was issued in 1993 and reaffirmed in 1998. The equipment covered by this Standard has been and continues to be a vital element of industrial, commercial, institutional and utility electrical distribution systems.Abstract
Revision Standard - Superseded.Low-voltage metal-enclosed switchgear-which contains either stationary or drawout, manuallyor electrically operated low-voltage ac or dc power circuit breakers in individual grounded metalcompartments, in three-pole, two-pole, or single-pole construction is covered. Rated maximum voltagelevels are 254V, 508V, or 635V (ac) and 300/325V, 800V, 1000V, 1200V, 1600V, or 3200V (dc). Thepreferred continuous current ratings of the main bus in ac designs are 1600A, 2000A, 3000A, 3200A,4000A, or 5000A. For dc designs, the preferred ratings are 1600A, 2000A, 2500A, 3000A, 4000A, 5000A,6000A, 8000A, 10000A, or 12000A. The switchgear may also contain associated control, instruments,metering, protective, and regulating devices as necessary. The standard deals with service conditions, ratings, temperature limitations, and classification of insulating materials, insulation (dielectric) withstand voltage requirements, test procedures, and application. Product Details
Published: 10/09/2002 ISBN(s): 9780738133041 Number of Pages: 55File Size: 1 file , 510 KB Product Code(s): STDSU95004