More info
Full Description
Lead corrosion inhibitor is necessary for water services utilizing lead-containing servicelines. Stannous chloride is a new corrosion inhibitor that can be used in a distribution system todepress the lead pipe corrosion. The application of low level stannous chloride (0.125 mg/L asSn) in water as a corrosion inhibitor not only avoids the addition of phosphate, which is an essentialnutrition to bacteria, but its toxicity can also inhibit drinking water bacterial activities or eveninactivate some bacteria while being safe for humans. Heterotrophs such as Escherichia coli.and Pseudomonas aeruginosa are susceptible to Sn toxicity, and autotrophs such asNitrosomonas europea, was less susceptible to Sn toxicity. In a laboratory test, the oxygenuptake rate of a P.aeruginosa batch in 1.0 mg/L SnCl2 decreased by 30% to 50%, and the oxygenuptake rate of a E.coli batch decreased almost a magnitude in 2.0 mg/L SnCl2. However, theoxygen uptake rate of N. europea had no significantly change in 2.0 mg/L SnCl2. Sn-contactexperiment was conducted also to test the viability of bacteria. In 1.0 mg/L SnCl2, 20 minutesinactivation rate ranged from approximately 60% to 95% at low bacterial concentration (106CFU per mL) suspensions for these two heterotrophs. And the 20 minutes N.europea inactivationrate appeared to be insignificant. Includes 11 references, figures. Product Details
Edition: Vol. - No. Published: 11/01/2007 Number of Pages: 8File Size: 1 file , 200 KB