1.1DV.1 Modification of Clause 1.1:This standard may be used as guide for
Replace "0,2 mm2 and 120 mm2 (AWG 24 and 250 kcmil)" with "0,1 mm2 and 120 mm2 (AWG 30 and 250 kcmil)".
1.1DV.2 Modification by adding the following:
This standard applies to insulation displacement terminals.
1.1DV.3 Modification by adding the following:
Terminal blocks with PEN function are not permitted.
- protective conductor terminal blocks requiring the fixing of special devices to the conductors, for example quick connect terminations or wrapped connections, etc.;Where applicable in this standard, the term "clamping unit" has been used instead of the term "terminal" This is taken into account in case of reference to IEC 60947-1.
- protective conductor terminal blocks providing direct contact to the conductors by means of edges or points penetrating the insulation, for example insulation displacement connections, etc.
1.1DV.4 Modification by adding the following:
This standard also applies to terminal blocks that have insulation piercing or displacement clamping units.
1.1DV.5 Modification by adding the following:
This standard specifies requirements for protective conductor terminal blocks with PE function up to 120 mm2 (250 kcmil) and for protective conductor terminal blocks with PEN function equal to and above 10 mm2 (AWG 8) with screw-type or screwless-type clamping units, primarily intended for industrial applications, in accordance with Annex DVB of item 1 in Annex DVA, National Electrical Code, NFPA 70 (for use in the USA), CSA C22.1-15 Canadian Electrical Code, Part I (for use in Canada), or NOM-001-SEDE, Electrical Installations (Utility) [for use in Mexico].